Water use and WUE — reading a Nordic climate claim
Does a cold Nordic climate make a Swedish hall water-free, or have you only been handed a winter photograph? The Green Grid’s 2011 white paper on Water Usage Effectiveness defines WUE as annual site water usage divided by IT-equipment energy, in litres per kilowatt-hour, and it splits a site metric from a source metric that also counts water used to make the electricity. ISO/IEC 30134-9:2022 is the later international KPI page for the same name. Commission Delegated Regulation (EU) 2024/1364 then writes a reporting formula WUE = W IN / E IT for operators of data centres with an installed IT power demand of at least 500 kW, and it says the public European database publishes averages, not every hall’s litre count. The IEA’s April 2025 Energy and AI report estimates about 560 billion litres of global data-centre water consumption a year, rising toward about 1 200 billion litres in 2030 in its Base Case, and it gives a United States 100 MW hyperscale example of about two million litres a day, more than 60 percent of it indirect. Those are global and US sentences. They are not a Luleå WUE and not a Kista seawater balance. Meta’s Luleå careers page describes outdoor-air cooling. Digital Realty’s STO1 page describes remote seawater cooling and “cooling-free” operation for over half the year. SMHI publishes station temperatures and 30-year normals. Weather is not a permit, and “cooling-free” is not a closed water file.

General orientation. Assess the specific project separately. Applies to: Readers testing a water-free, free-cooling or Nordic-climate sentence on a Swedish hall file.
Reading order
Start with the water object, not with the climate slogan. Write whether anyone has named make-up water, humidification, evaporative rejection, a once-through loop, seawater, a municipal network or no on-site water at all. Then write whether the number, if any, is a design take, a measured year, or a marketing zero. Only then ask which metric name is in play. WUE is not PUE. Site WUE is not source WUE. The Green Grid’s litres per kilowatt-hour are not automatically the same cell as the Union reporting ratio of cubic metres to megawatt-hours.
Keep legal and technical sentences apart. Naturvårdsverket’s Environmental Code pages open if abstraction or discharge is vattenverksamhet. A WUE cell does not classify that activity. SMHI’s temperature series describe climate. They do not sign a cooling plant and they do not close a municipal water conversation. ASHRAE’s liquid-cooling vocabulary stays on the cooling page. Bidding areas SE1 to SE4 do not allocate litres.
Then classify the climate claim. Outdoor air in Luleå, seawater wording in Kista and a SMHI normal for a named station are three different objects. A northern winter can reduce mechanical-cooling hours. It does not prove a measured WUE of zero, and it does not travel to Staffanstorp as a permit.
- Name the water object before the climate slogan.
- Label design, measured or marketing.
- Keep Green Grid units, ISO KPI language and Union reporting cells apart.
- A SMHI normal is weather, not a permit.
What WUE actually measures
The Green Grid’s 2011 paper is the dated industry definition. WUE is annual water used on site — including humidification and water evaporated on site for energy production or cooling — divided by IT-equipment energy. WUEsource adds water used off site to produce the electricity. A hall that rejects heat only to outdoor air can still have humidification or a source-water cell. A zero on a slide that does not name the boundary is not a measured site WUE.
ISO/IEC 30134-9:2022 specifies WUE as a use-phase KPI, introduces measurement categories, and warns that the metric is not a standalone comprehensive efficiency score and does not account for water-quality change outside the data-centre boundary. The ISO landing page is a standard abstract. It is not a Swedish statutory table and this page will not reprint a paid standard as if it were a municipal decision.
Delegated Regulation (EU) 2024/1364 is a reporting rule. Article 1 sets the scope at an installed IT power demand of at least 500 kW. Annex language measures total water input W IN in cubic metres with CEN/CENELEC EN 50600-4-9 WUE Category 2, or Category 1 if needed, and potable water W IN-POT. The sustainability indicator is WUE = W IN / E IT with E IT in megawatt-hours. The public European database, the regulation says, is aggregated: Member State and Union averages for WUE, not a named Swedish hall litre. A reporting duty is not a measured Falun year.
The IEA’s 2025 report is useful because it refuses a single thirst number. Box 5.4 says water use varies with cooling technology, local climate and the electricity source; about two-thirds of 2023 global consumption sat with energy supply, about one quarter with direct cooling, and the rest with manufacturing. Direct-expansion cooling, the report says, is many times less water-intensive than airside economisers and adiabatic systems with water-cooled chillers. Those are IEA estimates. They are not a Swedish campus census and they are not a WUE for Meta’s Luleå page.
What named primary sources show
Meta’s cited Luleå page remains the clearest Swedish outdoor-air sentence in this register. It is an operator description of one northern campus operational from 2013, with local hydropower. It does not publish a WUE, an annual litre take, or a water-permit decision. The 2011 Associated Press notice about Arctic chill bringing Facebook to Sweden is a siting story. It is not a measured water year.
Digital Realty’s STO1 page says the Stockholm halls run cooling-free for over half the year using remote seawater cooling. That is operator language about a Kista plant. Seawater is still water. “Cooling-free” is not a WUE of zero and not proof that abstraction, discharge or a municipal network conversation is closed. STACK’s live STO01 campus page states 18 MW, eight acres and one building. It does not, on that page, publish a WUE. atNorth SWE01 names liquid cooling and Exergi recovery, not a litre balance. GleSYS’s 1 October 2020 Falkenberg notice is a heat-delivery start, not a water census.
SMHI’s temperature pages and its annual-and-monthly statistics are the official Swedish climate series. They publish station observations and normals on a 30-year World Meteorological Organization period. They do not publish a data-centre WUE and they do not replace a cooling drawing. The Commission energy-performance page already in this register remains reporting context, including the Union rating scheme. It does not fill a missing Swedish hall litre.
A matrix instead of a climate score
Draw one page with water states in rows and evidence in columns. No on-site water, humidification only, evaporative rejection, seawater or once-through, and a named Environmental Code paper are different rows. Design drawing, measured period, operator marketing and Union reporting are different columns. Empty cells stay empty. A Nordic winter is not a column.
Do not invent a Swedish WUE league table from Meta’s outdoor air, Digital Realty’s seawater sentence, atNorth’s liquid loop or the IEA’s US 100 MW example. Those remain different objects from different years and methods.
| Water state | What a source can show | What this page will not invent |
|---|---|---|
| Outdoor-air / free cooling | An operator description of an air-side plant | A national water-free score |
| Seawater or once-through | A named loop on a dated operator page | A WUE of zero from “cooling-free” |
| Evaporative or adiabatic | A drawing of make-up and drift | An IEA US litre copied to SE1 |
| Reported WUE | Metric, boundary, period and method | A Swedish hall litre from the Union average |
Common misreads
The first misread is to treat a Nordic winter as a water permit. SMHI series are climate. Naturvårdsverket still opens if the activity is classified. The second is to treat “cooling-free” or outdoor air as a measured WUE of zero. Humidification, seawater, make-up and source water can still sit in the file. The third is to paste the IEA’s two-million-litre US example onto Horndal, Falun or SWE04.
The fourth is to compare Green Grid L/kWh with the Union m³/MWh cell as if they were already the same number. The fifth is to treat an aggregated Member State WUE, once published, as a named hall result. The sixth is to use hydropower in Luleå as proof that the cooling loop uses no water. Fuel mix stays in the energy-mix cell.
What to ask next
Ask for the water object, the source, the annual and peak volumes, and whether any figure is designed or measured. Ask which WUE definition is in the slide — Green Grid site, Green Grid source, ISO category, or Union W IN / E IT — and for which period. Ask whether seawater or a municipal network is in the loop. Ask which Environmental Code paper, if any, has been opened.
Then open the parent cooling page, the water-and-cooling approvals page, the liquid-cooling page and the energy-efficiency page. If the operator will not name the litre or the rejection neighbour, record the gap. Do not fill it from a climate slogan or from an IEA US example.
- Water object, source, annual and peak volumes.
- WUE name, boundary, period and unit.
- Design versus measured labelled.
- Climate series kept as weather.
- No invented Swedish WUE league table.
What this does and does not prove
This page proves that a Nordic climate is not a water exemption and not a WUE. It proves that The Green Grid published a 2011 site-versus-source definition, that ISO/IEC 30134-9 exists as a KPI standard, that the Union reporting rule uses W IN / E IT for halls at or above 500 kW IT demand, and that the IEA published global and US water estimates in April 2025.
It does not prove a best Swedish cooling water technology. It does not publish a national WUE, a Luleå litre year, or a Kista seawater permit. It does not treat Digital Realty’s “cooling-free” sentence as zero water. It does not convert operator PUE figures into water scores.
Unknown litres, unknown loops and unknown Environmental Code papers stay unknown. Point to the named source gap. Until a later primary source adds a measured Swedish WUE with a boundary and a year, the climate is weather rather than a water permit.
Sources
- Water Usage Effectiveness (WUE): A Green Grid data-center sustainability metric (WP#35) — The Green Grid, 2011-03-01. Checked 2026-09-12.
- ISO/IEC 30134-9:2022 — Data centres key performance indicators — Part 9: Water usage effectiveness (WUE) — ISO, 2022-03-01. Checked 2026-09-12.
- Commission Delegated Regulation (EU) 2024/1364 — first phase of a common Union rating scheme for data centres — European Union, 2024-03-14. Checked 2026-09-12.
- Energy performance of data centres — European Commission, 2026-01-01. Checked 2026-09-10.
- Energy and AI — International Energy Agency, 2025-04-10. Checked 2026-09-12.
- Temperature observations and climate data — SMHI (publication date not stated). Checked 2026-09-12.
- Annual and monthly statistics — temperature, wind, precipitation and sunshine — SMHI, 2024-10-22. Checked 2026-09-12.
- Welcome to Facebook Luleå Sweden — Meta Careers, 2013-06-12. Checked 2026-09-10.
- Arctic chill brings Facebook data center to Sweden — Associated Press / Phys.org, 2011-10-27. Checked 2026-09-10.
- Stockholm STO1 — Digital Realty (publication date not stated). Checked 2026-09-12.
- STO01 — Stockholm — STACK Infrastructure (publication date not stated). Checked 2026-09-12.
- SWE01 Stockholm metro site — atNorth, 2026-01-01. Checked 2026-09-10.
- Surplus energy from a new data center is transformed into district heating — GleSYS / Mynewsdesk, 2020-10-01. Checked 2026-09-10.
- Environmental assessment and permits — Naturvårdsverket, 2026-01-01. Checked 2026-09-10.
- Emergence and Expansion of Liquid Cooling in Mainstream Data Centers — ASHRAE Technical Committee 9.9, 2021-01-01. Checked 2026-09-12.